| ====== Moxa IO device through Modbus ====== | ====== Moxa IO device through Modbus ====== |
| TERRA 4D comes with a Modbus plugin which allows integration of different types of Modbus devices. | TERRA 4D comes with a Modbus plugin which allows integration of different types of Modbus devices. Here we focus on Moxa devices. |
| |
| ===== Supported features: ===== | ===== Supported features: ===== |
| |
| ===== Installation instructions: ===== | ===== Installation instructions: ===== |
| | === Webbrowser: === |
| | * Connect the Moxa device to Ethernet and open the browser |
| | * Connect to address 192.168.127.254 which is normally the default IP address of the Moxa devices |
| | * Main things to configure: Password, Security/Service Setting/Modbus!!!, Network/LAN, IO/Channel Mode (especially for DIOs) |
| | * alternatively you can use IOxpress software |
| === Moxa IOxpress software: === | === Moxa IOxpress software: === |
| - Connect the Moxa device to Ethernet and install the Moxa IOxpress software (download from Moxa website) | * Connect the Moxa device to Ethernet and install the Moxa IOxpress software (download from Moxa website) |
| - Start the Moxa IOxpress and select Device/Search... to find your device | * Start the Moxa IOxpress and select Device/Search to find your device |
| - Main things to configure: Password, Security/Service Setting/Modbus, Network/LAN, IO/Channel Mode (especially for DIOs) | * Main things to configure: Password, Security/Service Setting/Modbus!!!, Network/LAN, IO/Channel Mode (especially for DIOs) |
| - on the Device Library page you find in the Deployment combobox the device actions, like up- and download of configuration files | * on the Device Library page you find in the Deployment combobox the device actions, like up- and download of configuration files |
| - on the Configuration Library page you can change all settings and store it to a local file | * on the Configuration Library page you can change all settings and store it to a local file |
| === TERRA 4D Configurator: === | === TERRA 4D Configurator: === |
| - create a subsystem plugin device Modbus with default settings | * create a subsystem plugin device Modbus with default settings |
| == Input: == | * Input: |
| - create a IO device of type Modbus and select SubType "Input" | * create a IO device of type Modbus and select SubType "Input" |
| - IP port: 502, Server address: 0, Start address: 0, Input number: 0...N | * IP port: 502, Server address: 0, Start address: 0, Input number: 0...N |
| == Output: == | * Output: |
| - create a IO device of type Modbus and select SubType "Output" | * create a IO device of type Modbus and select SubType "Output" |
| - IP port: 502, Server address: 0, Start address: 0, Output number: 0...N | * IP port: 502, Server address: 0, Start address: 0, Output number: 0...N |
| | * Input register (e.g. for PWM counter): |
| | * create a IO device of type Modbus and select SubType "Input register" |
| | * IP port: 502, Server address: 0, Start address: 17, Input number: 0...N |
| | * Analog Input: |
| | * create a IO device of type Modbus and select SubType "Analog Input" |
| | * IP port: 502, Server address: 0, Start address: 520, Input number: 0...N |
| | * Configure low/high threshold depending on application to generate events when reading goes outside the expected range. |
| |
| ===== Other hints ===== | ===== Other hints ===== |
| Login to the browser page of the Moxa device to see the status of inputs and outputs and also other information. | * Within the device web page, in the main menu, within User-Defined Modbus Addressing, select Analog Inputs, Digital Input/Outputs (or similar): |
| | * Make sure "Enable Modbus/TCP Slave Protocol" is enabled |
| | * Within the table all the addresses of the available data points are listed. E.g. "AI Scaling Value (Float)" at "0520" as Input Register (read-only), Reference Address "30521" |
| | * Within Terra4D use "Analog Input" with the address 520 (the 30000 is automatically added by selecting Analog Input). |
| | |
| | * [[https://store.chipkin.com/products/tools/cas-modbus-scanner|CAS Modbus Scanner]] Tool to read/check Modbus device and see the values returned by the device. |